Symptom Tree t078
| Cause | Correction |
|---|
|
Battery voltage is low |
Inspect the batteries and the unswitched battery supply circuit. Refer to Procedure 013-009, and Procedure 019-087 in the Troubleshooting and Repair Manual Electronic Control System ISM and QSM11 Engines, Bulletin |
![]() |
|
Battery cables or connections are loose, broken, or corroded (excessive resistance) |
Check the battery cables and connections. Refer to Procedure |
![]() |
|
Engine-driven units are engaged |
Disengage engine-driven units. |
![]() |
|
Lubricating oil temperature is below specificationProcedure |
Install an oil pan heater, or drain the oil and fill the system with warm oil. |
![]() |
|
Lubricating oil does not meet specifications for operating conditions |
Change the oil and filters. Refer to Procedure |
![]() |
|
Crankshaft rotation is impaired |
Check the crankshaft for ease of rotation. Refer to Procedure |
![]() |
|
Battery capacity is below specification |
Refer to Procedure |
![]() |
|
Battery cables are not the correct gauge or length |
Replace the battery cables with larger gauge or shorter length cables. Refer to Procedure |
![]() |
|
Starting circuit component is malfunctioning |
Check the starting circuit components. Refer to the OEM service manual. |
![]() |
|
Starting motor pinion or ring gear is damaged |
Remove the starting motor, and inspect the gear. Refer to Procedure |
![]() |
|
Hydraulic lock in a cylinder |
Remove the injectors and rotate the crankshaft. Look for the source of fluid in the cylinder. Refer to Procedures |
![]() |
|
Internal engine damage |
Analyze the oil and inspect the filters to locate an area of probable damage. Refer to Procedure |
